Improved event based method for harmonic impedance assessment
Loading...
Date
Researcher ID
Supervisors
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE
Record Identifier
Abstract
The quantification of harmonic emission requires an accurate model of the network harmonic impedances. A number of techniques have been proposed for the assessment of the network harmonic impedances to be practical and noninvasive. This paper presents an improved noninvasive assessment technique for the evaluation of network harmonic impedances. Rapid voltage change events are evaluated to determine their validity for harmonic impedance calculations. Data filters based on the network under consideration is also introduced. Harmonic impedance values are derived for each validated event and the statistical median of the results is used to represent the network harmonic impedances. It enables an online and noninvasive tracking of network configuration and validation of simulated results
Sustainable Development Goals
Description
Citation
Serfontein, D. et al. 2016. Improved event based method for harmonic impedance assessment. Proceedings of the IEEE International Workshop on Applied Measurements for Power Systems (AMPS), 28-30 Sept: # 7602807. [https://doi.org/10.1109/AMPS.2016.7602807]